Low Price 12V38AH UPS Battery For Fire Safety Power Protection Serious Computing Systems Hospital Power Emergency Power Supply

Low Price 12V38AH UPS Battery For Fire Safety Power Protection Serious Computing Systems Hospital Power Emergency Power Supply

Basic Info Model NO.: 12V38AH Usage: UPS, Electric Power, Lighting, Electric Bicycle, Boat Discharge Rate: High Discharge Rate Electrolyte: Acid Rechargeable: Chargeable Brand Name: GOLD LIGHT POWER Advantage 1: High Capacity, Good Quality Production Lead-Time: 15~30 Days After Deposit...

Product Details

Basic Info

Model NO.: 12V38AH           

Usage: UPS, Electric Power, Lighting, Electric Bicycle, Boat

Discharge Rate: High Discharge Rate                       

Electrolyte: Acid

Rechargeable: Chargeable                      

Brand Name: GOLD LIGHT POWER

Advantage 1: High Capacity, Good Quality           

Production Lead-Time: 15~30 Days After Deposit

Trademark: GOLD LIGHT POWER                 

Origin: Guangdon, China(Mainland)

Type: Lead-Acid Batteries                          

Nominal Voltage: 12V

Shape: Square Battery                               

Installation: Fixed

Color: Any Color The Customer Needs        

Quality Standard: ISO9000, CE, RoHS, MSDS, Soncap, Coc/Voc, IEC Test

Advantage 2: High Performance, with Low Price               

Packing Quantity: 1PCS/Box

Specification: CE\RoHS\COC\VOC\SONCAP                

HS Code: 8507200000


Product Description

CE Approve AGM vrla Battery 12V 38ah


Low Price 12V38AH UPS Battery For Fire Safety Power Protection Serious Computing Systems Hospital Power Emergency Power Supply

SPECIFICATIONS

Cells Per Unit

6

Voltage Per Unit

12

Capacity

12V38AH@10hr-rate to 1.80V per cell @25ºC

Operating Temperature Range

Discharge: -20 ºC~60ºC  
Charge: 0ºC~50ºC
Storage: -20ºC~60ºC

Normal Operating Temperature Range

25ºC±5ºC

Float charging Voltage

13.6 to 13.8 VDC/unit Average at 25ºC

Equalization and Cycle Service

14.6 to 14.8 VDC/unit Average at 25ºC

Self Discharge

Batteries can be 
stored for more than 6 months at 25ºC. Self-discharge 
ratio less than 3% per month at 25ºC. Please charge 
batteries before using.

Container Material

A.B.S. UL94-HB, UL94-V0 Optional.


Battery Use and Maintenance:
1.With constant voltage charging  
2.In floating charge ,the voltage is 2.23 to 2.27/cell

3.In cycle using charge. the voltage is 2. 35 to 2. 45/ceIl.Maxinum current is less than 25%
4.When the battery is in use, be sure to tighten the screws of the terminal block, so as to avoid sparks and Poor contact
5.Don' t be used close to sources of hear and open flames
6.Don' t be used in low temperature when battery is using.
7.If there is leakage and breakage, should  be replaced immediately.